The National Fire Protection Association (NFPA) writes the codes that shape how hospitals and other healthcare buildings are designed, built and maintained. CMS, The Joint Commission and most states enforce them. Here are the requirements that matter most, and the ones surveyors cite most often.

Which editions apply

For Medicare and Medicaid surveys, CMS enforces the 2012 editions of NFPA 101, Life Safety Code, and NFPA 99, Health Care Facilities Code. Those codes in turn bring in other NFPA standards at the editions they reference, including:

  • NFPA 10, Portable Fire Extinguishers (2010)
  • NFPA 13, Installation of Sprinkler Systems (2010)
  • NFPA 25, Inspection, Testing and Maintenance of Water-Based Systems (2011)
  • NFPA 70, National Electrical Code (2011)
  • NFPA 72, National Fire Alarm and Signaling Code (2010)
  • NFPA 80, Fire Doors and Other Opening Protectives (2010)
  • NFPA 110, Emergency and Standby Power Systems (2010)

A state or city may enforce newer editions at the same time, so a project often has to satisfy two sets of rules. CMS proposed moving to the 2024 editions in November 2026; see CMS facility requirements.

NFPA 101: Life Safety Code

Health care occupancies are covered by Chapter 18 for new construction and Chapter 19 for existing buildings. The strategy is “defend in place”: patients who cannot easily evacuate are protected by moving them horizontally to a safe compartment.

  • Smoke compartments. Floors are divided by smoke barriers into compartments of no more than 22,500 square feet, with no more than 200 feet of travel to a smoke barrier door.
  • Refuge area. Each compartment must hold patients moved from the next one: at least 30 net square feet per hospital patient.
  • Corridors. In new hospitals, corridors used by patients must be at least 8 feet wide, and must be kept clear.
  • Suites. Patient care and sleeping suites have area and travel distance limits, so large departments must be planned around them.
  • Fire and smoke barriers. Every penetration by pipes, ducts or cables must be properly sealed.

NFPA 99: Health Care Facilities Code

  • Risk categories. Building systems are classified in Categories 1 to 4, based on the risk to patients if the system fails. The category sets the level of design and redundancy required.
  • Essential electrical system. Hospitals need life safety, critical and equipment branches on emergency power, with power restored within 10 seconds.
  • Medical gas and vacuum. Piping, alarms, zone valves and testing must meet the code, and changes must be verified before use.

Emergency power testing (NFPA 110)

  • Monthly: diesel generators run under load for at least 30 continuous minutes, at no less than 30% of nameplate rating or the manufacturer’s recommended exhaust temperature, with tests 20 to 40 days apart.
  • Every 36 months: a continuous 4-hour load test for Level 1 systems.
  • Transfer switches are tested monthly, and every test needs a written record.

Fire doors (NFPA 80)

Since the 2012 Life Safety Code was adopted, every fire door assembly in a health care occupancy must be inspected and tested annually under NFPA 80-2010, by a qualified person, with written records. CMS required full compliance by January 1, 2018.

Sprinklers, alarms and extinguishers

  • Sprinklers (NFPA 13 and 25): installed to code, kept clear of storage, and inspected and tested on weekly, monthly, quarterly and annual schedules.
  • Fire alarm (NFPA 72): devices and notification inspected and tested on set schedules, coordinated with smoke compartments.
  • Extinguishers (NFPA 10): inspected monthly and maintained annually.

Where facilities are most often cited

  • Unsealed penetrations in fire and smoke barriers
  • Fire doors that don’t latch or close, or missing annual inspection records
  • Storage in corridors or too close to sprinkler heads
  • Gaps in generator, sprinkler and fire alarm testing records
  • Life Safety Plans that no longer match the building

How JSMA helps

JSMA inspects existing facilities and reviews plans for new ones against NFPA, CMS, Joint Commission and Illinois licensure requirements, prepares Life Safety Plans, and writes plans of correction. See our code and licensure services or talk to us about your facility.

Sources

This article is a general overview, not a substitute for the codes or for professional review. Requirements vary by occupancy, construction date and jurisdiction.

JSMA Healthcare

Let’s plan what’s next.

Start a conversation

Search JSMA

Privacy preferences

Necessary security features stay active. Optional services are off until you allow them.

Protects forms against abuse and remembers these preferences.

Not in use on this website.

Not in use on this website.

Read the Privacy Policy